Mar-Bal Glastic® Light Weight Standoff Insulator, 5000 V

ID: STAOFF46101E Mfr ID: 46101-E
Manufactured by: Mar-Bal
Molded Insulators have a higher resistance to heat and moisture when compared to regular plastic insulators. These molded insulators also have closer height tolerances and higher shatter resistance when compared to ceramic insulators.

Select by Part Number

OR
Select Options Below
Voltage Rating
This Item is Flagged for Deletion. To find out more about this item, please contact your local sales office or search for other options. This Item is Flagged for Deletion. You may view Suggested Replacements for this item, contact your local sales office or search for other options.
  • Brand name :  Marbal
  • Trade Name :  Glastic®
  • Series :  Glastic® 46-1E
  • Item Name :  Standoff Insulator
  • Short Desc :  STANDOFF,4610,5KV,3.5"H,3/8"X16X9/16
  • UNSPSC :  39121721

Hi-Pot tested to assure electrical reliability. Wet or dirty conditions may require derating an insulator.

Performance Details
Flame Retardant Yes 
Track Resistance 600  min
Design & Construction
Material Polyester 
General Features
Type Light Weight 
Electrical Properties
Voltage Rating 5000  V
Physical Properties
Arc Resistance 180  sec
Height Tolerance +/-0.015 Inch 
Shape Round 

Mar-Bal Glastic® Light Weight Standoff Insulator, 5000 V Catalog 

Features :

  • Glastic standoff insulators are molded of underwriters laboratories incorporated® (UL) recognized flame resistant fiberglass-reinforced thermoset polyester molding compound
  • They feature shatter resistance and closer height tolerances than commonly available in porcelain insulators
  • Moisture and heat-resistance properties of glastic insulators are higher than those of conventional plastic insulators
  • Insulators mounted within a suitable electrical cabinet are considered indoors even though the cabinet itself is outdoors
  • An insulator will withstand its rated voltage continuously but industry standards or other specifications may require a different spacing from conductor to ground for a particular voltage

Applications :

  • Glastic Insulators are Primarily Intended to be Used Indoors or Inside a Suitable Enclosure